CS125 DN25 MANIFOLDS

Bilateral distribution manifolds in stainless steel compatible with CS125 DN25 distribution groups.

Suitable for heating and cooling systems, CS125 DN25 MANIFOLDS are supplied with closed-cell expanded PE, removable and inspectable with a convenient Velcro closure. Designed to be paired with CS125 DN25 distribution groups, it allows for the regulation and distribution of energy in modern systems. 2” manifolds and DN25 outlets ensures high flow rates and low pressure drops. Installed downstream of boilers or heat pumps, in combination with hydraulic separators and tanks from chapter 1, it manages the distribution in the secondary circuits of heating or cooling systems. Used individually with the wide range of accessories, it allows for multiple applications.

The supply includes:

  • Stainless steel AISI 304 distribution manifold;
  • Pair of union fittings with system connection Ø1” F;
  • Pair of caps with flat gasket;
  • Wall mounting (screw and anchor not included);
  • 15 mm closed-cell expanded PE insulation shell.

Performance

  • Nominal flow rate = 3 m3/h – max 4.5m3/h;
  • Max power = 50 kW BOILER;
  • Max power = 18 kW HEAT PUMP.

GENERAL TECHNICAL DATA

  • Operating temperature range: +5 °C /+80 °C
  • Maximum operating pressure: 6 bar
  • Connections: IN 1″ F (union fitting) – OUT 1″ 1/2 F SP
  • Main body: Ø 2”
  • Fluids: water – water/glycol mixtures (max 30%)

Materials

  • Manifold: AISI 304
  • Fittings: Brass UNI EN 12164 – CW614N
  • Hydraulic seals: EPDM
  • Insulation: PE 15mm, Density 60 kg/m3, T. Conduct. 0.04 W/mK

PRESSURE LOSS

The pressure drops of the 1+1 and 2+2 manifolds are equal to those of the 1-way and 2-way manifolds, respectively.

REF. CS125

1 DN25

2 DN25

3 DN25

4 DN25

5 DN25

1+1 DN25

2+2 DN25

A

225

385

545

705

865

225

385

Packaging L x B x H (mm)

290 x 240 x 150

450 x 240 x 150

610 x 240 x 150

930 x 240 x 160

930 x 240 x 160

290 x 240 x 150

450 x 240 x 150

Packaging weight (kg)

3.00

4.60

6.30

8.30

9.90

3.30

5.40

REF. CS80

1 DN25

2 DN25

3 DN25

A

225

385

545

Packaging L x B x H (mm)

290 x 240 x 150

450 x 240 x 150

610 x 240 x 150

Packaging weight (kg)

3.00

4.60

6.30

REF. CS80

4 DN25

5 DN25

1+1 DN25

2+2 DN25

A

705

865

225

385

Packaging L x B x H (mm)

930 x 240 x 160

930 x 240 x 160

290 x 240 x 150

450 x 240 x 150

Packaging weight (kg)

8.30

9.90

3.30

5.40

PRODUCT LIST

DESCRIPTION

CODE

CS125 DN25 manifold – 1 outlet

415000

CS125 DN25 manifold – 2 outlets

415001

CS125 DN25 manifold – 3 outlets

415002

CS125 DN25 manifold – 4 outlets

415003

CS125 DN25 manifold – 5 outlets

415004

CS125 DN25 manifold – 1+1 outlets

415011

CS125 DN25 manifold – 2+2 outlets

415022

ACCESSORIES LIST

REF.

DESCRIPTION

CODE

1

RED Isolation VALVE KIT Ø 1” F X 1” 1/2 F (1 PC.)*

712106

RED Isolation VALVE KIT ø 1” 1/4 F x 1” 1/2 F (1 pC.)

712108

2

 

BLUE Isolation VALVE KIT Ø 1″ F x 1″ 1/2 F WITH CHECK VALVE (1 PC.)*

712110

BLUE Isolation VALVE KIT Ø 1″ 1/4 F x 1″ 1/2 F WITH CHECK VALVE (1 PC.)

712115

BLACK Isolation VALVE KIT Ø 1″ F x 1″ 1/2 F (1 PC.)*

712111

BLACK Isolation VALVE KIT Ø 1″ 1/4 F x 1″ 1/2 F (1 PC.)

712116

RED VALVE KIT Ø 1″ 1/2 M x 1″ 1/2 F (1 PC.)*

712107

BLUE VALVE KIT Ø 1″ 1/2 M x 1″ 1/2 F WITH CHECK VALVE (1 PC.)*

712109

3

BLACK VALVE KIT Ø 1″ 1/2 M x 1″ 1/2 F (1 PC.)*

712113

4

 

Isolation VALVE SHELL KIT Ø 1” F / 1” 1/4 F X 1” 1/2 F (1 PC.)**

712114

Isolation VALVE SHELL KIT Ø 1″ 1/2 M x 1″ 1/2 F (1 PC.)**

712117

FITTINGS KIT Ø 1” 1/2 M X 1” F (2 PC.)***

712112

5

PLUGS KIT Ø 1” 1/2 M (2 PC.)

903040

6

UNION FITTINGS CS MANIFOLD KIT (2 PC.)

903041

7

Isolation VALVES FOR CS MANIFOLD INTERCONNECTION KIT (2 PC.)

903031

8

Nickeled brass Union fitting kit Ø 1” 1/4 M x 1” 1/2 F (2 Pc.)

903052

9

UNION FITTINGS CS MANIFOLD KIT (2 PC.)

934001

ISOLATION VALVES FOR CS MANIFOLD INTERCONNECTION KIT (2 PC.)

712020

10

NICKELED BRASS UNION FITTING KIT Ø 1” 1/4 M X 1” 1/2 F (2 PC.)

903006

* It is recommended to combine it with the fittings kit code 903031.
** Insulating material for the product installation in cooling.
*** It is recommended to use the fittings to connect the product directly to the system pipes.
In case of configuration with 1+1 and 2+2 manifold, it is mandatory to purchase 1 (or 2) standard groups and 1 (or 2) reverse groups. It is mandatory to purchase the reverse groups also if the supply and return on the manifold are reversed.

Paths of the fluid in communication between supply and distribution. Equal symbols identify the paths in communication.

Typical configuration:

= Supply
= Return

Any configurations can be achieved by changing, when necessary, the position of the headers, plugs, and insulation.
The symbols in the images represent the communicating chambers.
Through specific fittings, the capped connections can also be used for connecting safety devices, system loading, etc.
The manifold is supplied for the installation of distribution groups with supply on the left and return on the right (see configuration 1 and 2).
The distribution groups are reversible during installation.

Note: The distribution groups, in one of the two directions (in the drawing, the one pointing upwards), must be of the INVERTED type (DX).